Smart-UPS Online 1000VA 230V (XRT1000-U/RM)

0 out of 5

RM1,140.00

SKU: XRT1000-U/RM Categories: Uncategorized, Uninterruptible Power Supply (UPS)
Compare

Description

𝐒𝐩𝐞𝐜𝐢𝐟𝐢𝐜𝐚𝐭𝐢𝐨𝐧𝐌𝐨𝐝𝐞𝐥                                       XRT1000-U/RM 

𝐂𝐚𝐩𝐚𝐜𝐢𝐭𝐲 (𝐕𝐀/𝐖𝐚𝐭𝐭𝐬)             1000VA/1000W

 

𝐏𝐡𝐚𝐬𝐞 𝐒𝐢𝐧𝐠𝐥𝐞                            phase with grounde with

 

𝐈𝐍𝐏𝐔𝐓

𝐍𝐨𝐫𝐦𝐢𝐧𝐚𝐥 𝐕𝐨𝐥𝐭𝐚𝐠𝐞                   200/208/220/230/240/Vac

𝐎𝐩𝐞𝐫𝐚𝐭𝐢𝐧𝐠 𝐯𝐨𝐥𝐭𝐚𝐠𝐞 𝐫𝐚𝐧𝐠𝐞

Low voltage of transferring to bypass

160Vac±5%@100%~80% load 140Vac±5%@80%~70% load 120Vac±5%@70%~60% load 110Vac±5%@60%~0% load (Ambient Temp. <35C)

 

Low threshold voltage of recovering from bypass

175Vac±5%@100%~80% load 155Vac±5%@80%~70% load 135Vac±5%@70%~60% load 125Vac±5%@60%~0% load (Ambient Temp. <35C)

 

𝐇𝐢𝐠𝐡 𝐯𝐨𝐥𝐭𝐚𝐠𝐞 𝐨𝐟 𝐭𝐫𝐚𝐧𝐬𝐟𝐞𝐫𝐫𝐢𝐧𝐠 𝐭𝐨 𝐛𝐲𝐩𝐚𝐬𝐬                    300Vac±5%

 

𝐇𝐢𝐠𝐡 𝐭𝐡𝐫𝐞𝐬𝐡𝐨𝐥𝐝 𝐯𝐨𝐥𝐭𝐚𝐠𝐞 𝐨𝐟 𝐫𝐞𝐜𝐨𝐯𝐞𝐫𝐢𝐧𝐠 𝐟𝐫𝐨𝐦 𝐛𝐲𝐩𝐚𝐬𝐬                       290Vac±5%

 

𝐎𝐩𝐞𝐫𝐚𝐭𝐢𝐧𝐠 𝐅𝐫𝐞𝐪𝐮𝐞𝐧𝐜𝐲 𝐑𝐚𝐧𝐠𝐞                     40~70Hz

𝐆𝐞𝐧𝐞𝐫𝐚𝐭𝐨𝐫 𝐈𝐧𝐩𝐮𝐭                                            Support

 

𝐎𝐔𝐓𝐏𝐔𝐓

𝐎𝐮𝐭𝐩𝐮𝐭 𝐕𝐨𝐥𝐭𝐚𝐠𝐞                  200/208/220/230/240/Vac

𝐏𝐨𝐰𝐞𝐫 𝐅𝐚𝐜𝐭𝐨𝐫                     1.0

𝐕𝐨𝐥𝐭𝐚𝐠𝐞 𝐑𝐞𝐠𝐮𝐥𝐚𝐭𝐢𝐨𝐧          ±1%

 

𝐅𝐫𝐞𝐪𝐮𝐞𝐧𝐜𝐲

𝐋𝐢𝐧𝐞 𝐦𝐨𝐝𝐞 (𝐒𝐲𝐧𝐜𝐡𝐫𝐨𝐧𝐢𝐳𝐞𝐝 𝐫𝐚𝐧𝐠𝐞)     47~53Hz or 57~63Hz

𝐁𝐚𝐭. 𝐦𝐨𝐝𝐞         (50/60±0.1)Hz

𝐂𝐫𝐞𝐬𝐭  3:1

𝐇𝐚𝐫𝐦𝐨𝐧𝐢𝐜 𝐃𝐢𝐬𝐭𝐨𝐫𝐭𝐢𝐨𝐧 (𝐓𝐇𝐃𝐯)                  <2% THD (Linear load) / <4% THD (Non-Linear load)

𝐖𝐚𝐯𝐞𝐟𝐨𝐫𝐦                                  Pure Sineswave

 

𝐓𝐫𝐚𝐧𝐬𝐟𝐞𝐫 𝐓𝐢𝐦𝐞

𝐀𝐂 𝐦𝐨𝐝𝐞 <-> 𝐁𝐚𝐭𝐭. 𝐌𝐨𝐝𝐞            Zero

𝐈𝐧𝐯𝐞𝐫𝐭𝐞𝐫 <-> 𝐁𝐲𝐩              4ms (Typical)

 

𝐁𝐀𝐓𝐓𝐄𝐑𝐘

𝐁𝐚𝐭𝐭𝐞𝐫  12V9AH

𝐍𝐮𝐦𝐛𝐞𝐫𝐬       2

𝐁𝐚𝐜𝐤𝐮𝐩 𝐓𝐢𝐦𝐞

Long run unit depends on the capacity of externel batteries

𝐓𝐲𝐩𝐢𝐜𝐚𝐥 𝐑𝐞𝐜𝐡𝐚𝐫𝐠𝐢𝐧𝐠 𝐓𝐢𝐦𝐞 (𝐒𝐭𝐚𝐧𝐝𝐚𝐫𝐝 𝐌𝐨𝐝𝐞) 4 hours recover to 90% capacity

𝐂𝐡𝐚𝐫𝐠𝐢𝐧𝐠 𝐕𝐨𝐥𝐭𝐚𝐠𝐞               27.4VDC±1%

𝐂𝐡𝐚𝐫𝐠𝐢𝐧𝐠 𝐂𝐮𝐫𝐫𝐞𝐧𝐭 (𝐌𝐚𝐱.)            1A or 2A

 

𝐒𝐘𝐒𝐓𝐄𝐌 𝐅𝐄𝐀𝐓𝐔𝐑𝐄𝐒

𝐋𝐢𝐧𝐞 𝐌𝐨𝐝𝐞 𝐁𝐚𝐭𝐭𝐞𝐫𝐲 𝐌𝐨𝐝𝐞

𝐀𝐦𝐛𝐢𝐞𝐧𝐭 𝐓𝐞𝐦𝐩. <𝟑𝟓 𝐂

105%~110%: UPS transfer to bypass after 10 minutes when the utility is normal

110%~130%: UPS transfer to bypass after 1 minute when the utility is normal

130%~150%: UPS transfer to bypass after 5 seconds when the utility is normal

>150%: UPS transfer to bypass immediately when the utility is normal

 

𝟑𝟓 𝐂 <𝐀𝐦𝐛𝐢𝐞𝐧𝐭 𝐓𝐞𝐦𝐩. <𝟒𝟎 𝐂

105%~110%: UPS transfer to bypass after 10 minutes when the utility is normal

110%~130%: UPS transfer to bypass after 1 minute when the utility is normal

>130%: UPS transfer to bypass immediately when the utility is normal

 

𝐒𝐡𝐨𝐫𝐭 𝐂𝐢𝐫𝐜𝐮𝐢𝐭                              Hold whole system

𝐎𝐯𝐞𝐫𝐡𝐞𝐚𝐭 𝐋𝐢𝐧𝐞 𝐦𝐨𝐝𝐞:       Switch to bypass; Back up mode: Shut down UPS immediately

𝐁𝐚𝐭𝐭𝐞𝐫𝐲 𝐋𝐨𝐰         Alarm and switch off

𝐄𝐏𝐎 (𝐎𝐩𝐭𝐢𝐨𝐧𝐚𝐥)      Shut down UPS immediately

𝐀𝐮𝐝𝐢𝐛𝐥𝐞 & 𝐕𝐢𝐬𝐮𝐚𝐥 𝐀𝐥𝐚𝐫𝐦𝐬        Line failure, Battery low, Overload, System fault

𝐂𝐨𝐦𝐦𝐮𝐧𝐢𝐜𝐚𝐭𝐢𝐨𝐧 𝐈𝐧𝐭𝐞𝐫𝐟𝐚𝐜𝐞       USB, RS232, SNMP card (optional), Relay card (optional)

 

𝐖𝐚𝐫𝐫𝐚𝐧𝐭𝐲                                                1 Years manufactory warranty.